Aluminum conductors are not acceptable. Specification 26 05 19 paragraph 2.01 states that all power conductors shall be copper and that aluminum conductors are not permitted at any size or in any location, including feeders and service entrance conductors. This is not a value engineering item and will not be reconsidered
Ask the project record a question. Get the paragraph and the page, or get told the record does not say.
Corbel searches 53 indexed passages across 23 documents on Brickell Bay Tower: specifications, RFIs, submittal reviews, ASIs, inspection reports and meeting minutes. It returns passages, never summaries, and it returns nothing rather than a guess.
3 cited passages · every term of the question matched against the indexed text
power conductors shall be copper. Aluminum conductors are not permitted at any size or in any location, including feeders and service entrance conductors. Minimum conductor size for branch circuits shall be 12 AWG. Conductors for branch circuits longer than 100 feet from panel to first outlet shall be increased one trade size
propose aluminum conductors in place of copper for the 400 amp and larger feeders serving the residential risers, sized in accordance with NEC ampacity tables with an appropriate upsizing. Please confirm acceptability and advise whether a credit to the Contract Sum would be expected