Inspection reportINSP-2026-131Floor flatness survey, levels 3 through 84 of 5 terms

Levels 3, 4, 6, 7 and 8 met the specified overall flatness of FF 35 and overall levelness of FL 25. Level 5 measured an overall FF of 31 and an overall FL of 22, with a local minimum FF of 19 in the north west quadrant between column lines

insp_131.pdf · page 2 of the documentSurvey resultsissued Aug 12, 2026 by Ballast Testing Laboratories
Inspection reportINSP-2026-131Floor flatness survey, levels 3 through 84 of 5 terms

deficient area on level 5 measures approximately 2,850 square feet. Correction by grinding or by an approved underlayment is required under 03 30 00 paragraph 3.12 at no additional cost. Retest of the corrected area is recommended before resilient flooring is installed

insp_131.pdf · page 4 of the documentRecommendationissued Aug 12, 2026 by Ballast Testing Laboratories
Specification03 30 00Cast-in-Place Concrete3 of 5 terms

Slabs scheduled to receive resilient flooring or thin set tile shall be finished to an overall flatness of FF 35 and an overall levelness of FL 25, with minimum local values of FF 24 and FL 17. Measure in accordance with ASTM E1155 within 72 hours of slab finishing. Areas failing

spec_033000_r1.pdf · page 22 of the documentsection 03 30 00 - 3.12Floor flatness and levelnessissued Jun 7, 2025 by Kessel Structural Engineersrevision 1