RFI

RFI-038

Concealed sprinkler heads in the loading dock

rfi_rfi_038.pdf · 3 pages · issued Jul 27, 2026 by Windward Fire Protection · Fire Protection

Indexed passages

page 1Question

The reflected ceiling plan shows an exposed structure ceiling at the loading dock, and specification 21 13 13 paragraph 2.06 requires concealed heads only in areas with a finished ceiling. The same paragraph requires dry pendent heads in the loading dock. Please confirm that exposed upright heads on a dry system are intended at the loading dock rather than concealed heads.

Cross references

DirectionRelationDocumentNote
this →references21 13 13 Wet-Pipe Sprinkler SystemsRFI-038 cites 21 13 13 paragraph 2.06