RFI-046

Firestop engineering judgement for clustered conduit penetration

rfi_rfi_046.pdf · 3 pages · issued Aug 17, 2026 by Everglade Electric · Electrical

Indexed passages

page 1Question

At the level 9 electrical room the riser penetration contains 14 conduits ranging from 1 inch to 4 inches within a 24 inch by 24 inch opening. We have not located a tested system for this combination of penetrant sizes and annular space. Please advise whether an engineering judgement from the firestop manufacturer will be accepted.

page 2Response

An engineering judgement will be accepted for this condition only. Specification 07 84 00 paragraph 1.05 permits an engineering judgement where no tested system exists, provided it is issued by the manufacturer's licensed engineer and submitted for the Architect's record before installation. Submit the judgement before the penetration is closed.

Cross references

DirectionRelationDocumentNote
this →references07 84 00 FirestoppingRFI-046 cites 07 84 00 paragraph 1.05