07 84 00

Firestopping

spec_078400_r1.pdf · 12 pages · issued Aug 3, 2025 by Ardent Architects · Architectural · revision 1

Indexed passages

page 407 84 00 - 1.05Tested systems required

Every through penetration and construction joint firestop shall be a system tested in accordance with ASTM E814 or UL 1479 for the specific assembly, penetrant type, penetrant size and annular space present in the field condition. Engineering judgements will be considered only where no tested system exists, shall be issued by the manufacturer's licensed engineer, and shall be submitted for the Architect's record before installation.

page 807 84 00 - 3.03Identification labels

Label each firestop within 6 inches of the penetration with a permanent label showing the manufacturer, the system number, the installer, the installation date and the F rating. Labels shall be legible without removing ceiling tiles or access panels.

Cross references

DirectionRelationDocumentNote
→ thisreferencesRFI-046 Firestop engineering judgement for clustered conduit penetrationRFI-046 cites 07 84 00 paragraph 1.05