Corbel

Ask the project record a question. Get the paragraph and the page, or get told the record does not say.

Corbel searches 53 indexed passages across 23 documents on Brickell Bay Tower: specifications, RFIs, submittal reviews, ASIs, inspection reports and meeting minutes. It returns passages, never summaries, and it returns nothing rather than a guess.

2 cited passages · every term of the question matched against the indexed text

Specification21 13 13Wet-Pipe Sprinkler Systems6 of 6 terms

Provide quick response pendent heads with a temperature rating of 155 degrees Fahrenheit in all residential and office areas. Provide intermediate temperature heads rated 200 degrees Fahrenheit within 12 inches of heat producing equipment and in all mechanical rooms. Provide dry pendent heads in areas subject to freezing and in the loadingdock. Concealed heads with factory finished cover plates are required in all areas with a finished ceiling

spec_211313_r1.pdf · page 13 of the documentsection 21 13 13 - 2.06Sprinkler head types by areaissued Jun 22, 2025 by Corso Fire Engineeringrevision 1
RFIRFI-038Concealed sprinkler heads in the loading dock4 of 6 terms

reflected ceiling plan shows an exposed structure ceiling at the loading dock, and specification 21 13 13 paragraph 2.06 requires concealed heads only in areas with a finished ceiling. The same paragraph requires dry pendent heads in the loading dock. Please confirm that exposed upright heads on a dry system are intended…loading dock rather than concealed heads

rfi_rfi_038.pdf · page 1 of the documentQuestionissued Jul 27, 2026 by Windward Fire Protection

Passages are ordered by how much of the question they cover, then by cover density within the passage. Nothing above was written by Corbel; each block is the stored text of the cited page with the matched terms marked.