ASI

ASI-006

Revised parapet detail, north elevation

asi_006.pdf · 4 pages · issued Jun 13, 2026 by Ardent Architects · Architectural · revision 0

Indexed passages

page 1Description of change

Raise the parapet at the north elevation between column lines 6 and 11 by 4 inches to provide the 8 inch minimum base flashing height required by specification 07 52 00 paragraph 3.04. Revised detail 7/A-501 attached. This ASI clarifies the Contract Documents and is issued at no change in Contract Sum and no change in Contract Time. Proceed with the work as revised.

page 3Attached details

Detail 7/A-501 revision 2, parapet section at north elevation, showing the raised concrete masonry parapet, revised coping, and continuity of the air barrier from the wall assembly to the roof membrane at the raised height.

Cross references

DirectionRelationDocumentNote
this →answersRFI-014 Parapet height at north elevation less than specified base flashing heightASI-006 issued in response to RFI-014
→ thispriced byCO-014 Parapet raise, north elevationCO-014 submitted against ASI-006
→ thisreferencesOAC-2026-31 Owner Architect Contractor meeting number 31Meeting minutes record completion of the ASI-006 parapet raise