RFIRFI-021Curtain wall deflection criteria at double height lobby5 of 5 terms

lobby curtain wall at the east elevation has a clear span of 21 feet 4 inches between floor slab and the transfer beam. Specification 08 44 13 paragraph 1.07 gives a deflection limit of L/240 plus one quarter inch for spans greater than 13 feet 6 inches. Applying that limit…foot 4 inch span yields a permissible deflection of 1.317 inches. Please confirm this is the intended limit for the lobby, as the mullion depth required to meet it exceeds the 10 inch depth shown on the architectural elevations

rfi_rfi_021.pdf · page 1 of the documentQuestionissued Jun 9, 2026 by Cordova Glass Systems
RFIRFI-021Curtain wall deflection criteria at double height lobby5 of 5 terms

L/240 plus one quarter inch is the correct and intended limit and is not waived at the lobby. The mullion depth shown on the architectural elevations is diagrammatic. Coordinate the required depth with the Architect before fabrication. A deeper mullion at this location is acceptable provided the exterior sightline is maintained

rfi_rfi_021.pdf · page 2 of the documentResponseissued Jun 9, 2026 by Cordova Glass Systems
SubmittalSUB-084413-02Curtain wall shop drawings, east and north elevations4 of 5 terms

Returned Revise and Resubmit. The lobby mullion shown at detail 4 on sheet S-12 is a 10 inch depth and calculates to a deflection of 1.63 inches at design wind load, exceeding the permissible 1.317 inches for the 21 foot 4 inch clear span under 08 44 13 paragraph 1.07. Increase

sub_sub_084413_02.pdf · page 1 of the documentReview actionissued Oct 29, 2025 by Cordova Glass Systemsrevision 1
Specification08 44 13Glazed Aluminum Curtain Walls3 of 5 terms

wind loads determined in accordance with the Florida Building Code, High Velocity Hurricane Zone, for the building height and exposure indicated on the structural drawings. Deflection normal to the plane of the wall shall not exceed L/175 of the clear span for spans up to 13 feet 6 inches, and L/240 plus

spec_084413_r3.pdf · page 7 of the documentsection 08 44 13 - 1.07Structural performance and deflectionissued Aug 13, 2025 by Ardent Architectsrevision 3